The DB2000 series is a 96 X 96mm digital indicating controller with the indicating accuracy of ±0.1% and the control cycle of approximately 0.1 seconds.
The configuration of highly functional system is enabled by various options including 2 transmission signal outputs, 2 communications ports and arbitrarily-allocation of digital inputs.
Highly-functional operation screen and settings screen.
Outstanding controllability.
Versatile control functions provided.
Communications 2-port type provided.
Transmission signal 2-output type available.
READY function provided.
DI arbitrarily-allocation.
Heater disconnection alarm.
Conforming to international safety standards and European directives (CE).
Conforming to RoHS
Model
Control mode(Output No.1)
DB2010B000
ON-OFF pulse type PID
DB2020B000
ON-OFF servo type PID(Standard load specification)
DB2030B000
Current output type PID
DB2050B000
SSR drive pulse type PID
DB2060B000
Voltage output type PID
DB2080B000
ON-OFF servo type(Very light load specification)
Input type
ThermocoupleB, R, S, K, E, J, T, N, WRe5-WRe26, W-WRe26, NiMo-Ni, CR-AuFe, PR5-20, PtRh40-PtRh20, Platinel II, U, L
DC voltage ±10mV, ±20mV, ±50mV, ±100mV, ±5V, ±10V
DC current0 to 20mA
Resistance thermometerPt100, JPt100, Old Pt100, JPt50, Pt-Co
Accuracy rating
±0.1% of measuring range ± 1 digit
*For details, refer to [Detailed specifications of accuracy ratings].
Reference temperature compensation accuracy
K, E, J, T, N, Platinel II --- ±0.5°C or a value equivalent to ±20µV, whichever is greater
(at ambient temperature of 23°C ± 10°C)
Others --- ±1.0°C or a value equivalent to ±40µV, whichever is greater
Sampling period
Approx. 0.1 seconds
Displays element
Upper display LED
Lower display LCD (with back light) 108 x 24 dots
Display content
Upper display: PV 5-digit, SV 5-digit, status indications, etc.
Lower display: MV, output status, setting screens, etc.
Control cycle
Approx. 0.1 seconds
Output type
ON-OFF pulse type, ON-OFF servo type, Current output type, SSR drive pulse type, Voltage output type
PID 8 types
P : 0 to 999.9%
I : 1 to 9999 seconds
D : 0 to 9999 seconds
A.R.W. (Anti reset windup)
High limit --- 0 to 100.0%
Low limit --- -100 to 0.0%
Number of alarm points
4 points
Alarm types
Absolute value alarm, deviation alarm, absolute value deviation alarm, setting value alarm, output value alarm, control loop abnormality alarm, FAIL, timer
Output signal
Relay output signal (a contact)
Rated power voltage
General power supply specifications 100 to 240VAC
24V power supply specifications 24VAC/24VDC
Rated power supply frequency
General power supply specifications 50/60Hz
24V power supply specification 50/60Hz (24VAC)
Maximum power consumption
General power supply specifications
Without options 100VAC 10VA/240VAC 15VA
24V power supply specifications
Without options 24VAC 10VA/24VDC 5W
Working temperature range
-10 to 50°C
Working humidity range
10 to 90%RH
Color
Gray or black
External dimensions
96 (H) x 96 (W) x 127 (D)
*The depth from the front panel is 120mm