The KP2000 series is a 96x96mm digital program controller with the indicating accuracy of ±0.1%, the control cycle of approximately 0.1 seconds and maximum 30 program patterns (maximum 19 steps/ pattern). The configuration of highly functional system is enabled by various options including 2 transmission signal outputs, 2 communications ports and arbitrarily-allocation of digital inputs/outputs.
Maximum 19 steps per pattern and maximum 30 sets of patterns.
Versatile control functions provided.
Communications 2-port type provided.
Transmission signal 2-output type provided.
DI/DO arbitrarily-allocation.
Output up to 8 points of time signals enabled.
Heater disconnection alarm.
Conforming to international safety standards and European directives (CE).
Conforming to RoHS
Model
Control mode(Output No.1)
KP2010C000
ON-OFF pulse type PID
KP2020C000
ON-OFF servo type PID(Standard load specification)
KP2030C000
Current output type PID
KP2050C000
SSR drive pulse type PID
KP2060C000
Voltage output type PID
KP2080C000
ON-OFF servo type(Very light load specification)
Input type
Thermocouple: B, R, S, K, E, J, T, N, WRe5-WRe26, W-WRe26, NiMo-Ni, CR-AuFe, PR5-20, PtRh40-PtRh20, Platinel II, U, L
DC voltage: ±10mV, ±20mV, ±50mV, ±100mV, ±5V, ±10V
DC current: 0 to 20mA
Resistance thermometer: Pt100, JPt100, Old Pt100, JPt50, Pt-Co
Accuracy rating
±0.1% of measuring range ± 1 digit
*For details, refer to [Detailed specifications of accuracy ratings].
Reference temperature compensation accuracy
K, E, J, T, N, Platinel II --- ±0.5°C or a value equivalent to ±20µV, whichever is greater
(at ambient temperature of 23°C ± 10°C)
Others --- ±1.0°C or a value equivalent to ±40µV, whichever is greater
Sampling period
Approx. 0.1 seconds
Displays element
Upper display LED
Lower display LCD (with back light) 108 x 24 dots
Display content
Upper display: PV 5-digit, SV 5-digit, status indications, etc.
Lower display: MV, output status, setting screens, etc.
Control cycle
Approx. 0.1 seconds
Output type
ON-OFF pulse type, ON-OFF servo type, Current output type, SSR drive pulse type, Voltage output type
Number of patterns
30 patterns
Pattern repetition ... Maximum 9999 times
Number of steps
19 steps/pattern
Step repetition ... Maximum 99 times
Control relations
PID 8 types
P : 0 to 999.9%
I : 1 to 9999 seconds
D : 0 to 9999 seconds
A.R.W. (Anti reset windup)
High limit --- 0 to 100.0%
Low limit --- -100 to 0.0%
Number of alarm points
4 points
Alarm types
Absolute value alarm, deviation alarm
Output signal
Relay output signal (a contact)
Rated power voltage
General power supply specifications 100 to 240VAC
24V power supply specifications 24VAC/24VDC
Rated power supply frequency
General power supply specifications 50/60Hz
24V power supply specification 50/60Hz (24VAC)
Maximum power consumption
General power supply specifications
Without options 100VAC 10VA/240VAC 15VA
24V power supply specifications
Without options 24VAC 10VA/24VDC 5W
Working temperature range
-10 to 50°C
Working humidity range
10 to 90%RH
Color
Gray or black
External dimensions
96 (H) x 96 (W) x 127 (D)
*The depth from the front panel is 120mm